Three types of UPS Technologies

Online Double Conversion Technology

An uninterruptible power supply using true online double conversion technology provides the highest level of power protection available. The Online UPS converts the 230V input AC mains supply to DC power, which is then used to charge the battery. The DC current flow is then fed through an inverter stage that reconstructs the 230V AC mains output. Because the AC output is completely regenerated, it will be completely free from any mains-borne interference such as spikes and voltage variations. The output voltage and frequency is controlled precisely, thus ensuring a clean and stable sine wave power output. Online UPS are able to withstand large fluctuations on the input voltage before transferring to battery power (typically 276V-184V) thus eliminating unnecessary battery discharges. Upon mains failure, transfer to battery power is seamless - no break. Online UPS also have various failsafe and self-diagnostic features that will instantly transfer the load onto mains power if there is a failure within the UPS hardware, or if the UPS is overloaded.

.

Advantages:

  • Continuous & total power conditioning
  • Failsafe/overload protection with static bypass facility
  • No break on mains failure
  • Wide input voltage tolerance
  • Recommended with Generator sets

Disadvantages:

  • More expensive than other types of UPS technology

Offline Standby Technology

During normal operation of an Offline UPS, the power flows straight through the unit and hence only RFI filtering is usually provided. When the input voltage fails or fluctuates outside of a pre-set tolerance window, the UPS detects this and a relay will close, allowing the UPS to start feeding UPS battery power via the inverter. The inverter is then switched on and a square, step or sine wave form output is supplied. Upon the return of mains power, the output is switched back onto mains and the inverter is turned off. Typically there will be a break of between 4-10 ms during the transfer to and from the battery mode.

Advantages:

  • Low cost
  • Silent operation when in standby
  • Efficient

Disadvantages:

  • Minimal power protection - only protects against a small percentage of problems
  • Poor output voltage regulation - sags and surges will be passed straight to the load
  • Break transfer to battery mode
  • No failsafe - UPS will drop the load if there is a high start-up current, overload or inverter failure


Line-Interactive Technology

line-interactive UPS operates in a very similar fashion to an offline UPS, except with the advantage of better filtering and output voltage boost/reduce features. It does not eliminating mains-borne interference, line-interactive technologies does reduce the impact of spikes, surges and sags by 'clipping' the peaks and valleys, boosting power or switching to battery back up. As with offline UPS, when the input voltage fails or fluctuates outside of a pre-set tolerance window, the UPS detects this and a relay will close allowing the UPS to start feeding battery power via the inverter. The inverter, in a good line-interactive UPS, will supply a sine wave output. Upon the return of mains power, the output is switched back onto mains and the inverter is turned off.

As with offline UPS, typically there will be a break on the transfer to and from battery mode, though usually this will be shorter than with an offline UPS. Some manufacturers will try to pass their line-interactive UPS off as online models by calling them 'digital online', 'inline' or 'online interactive' - make sure you know what technology the UPS you are buying actually uses.

Advantages:

  • Lower cost than online
  • Gives better protection than offline
  • Silent operation when in standby
  • Efficient

Disadvantages:

  • Fluctuations, such as spikes, can still be passed straight to the load
  • Break on transfer to battery mode.
  • No failsafe - UPS will drop the load if there is a high start-up current, overload or inverter failure

Generator & UPS Compatibility

Due to the nature of the supply from a Generator we recommend utilizing Online Double Conversion Technology UPS. Online UPS have improved input frequency and voltage tolerance over non-online technology, therefore preventing frequent switching to battery power which maximizes battery life and UPS reliability. Because Online Double Conversion Technology completely regenerates the AC output it will be completely free from interference such as spikes and voltage variations which may adversely affect IT or other types of sensitive equipment.

Non-online UPS will often work, although intermittently, with a Generator supply but will ultimately fail. Usually the UPS failure happens under load or when the Generator is providing the main supply. A Generator backed supply is often a critical one and necessitates the highest form of protection, Online Double Conversion Technology provides this protection.

UPS Eco-mode and Energy Saver Systems

High efficiency is now a standard in UPS design. Consider the following when selecting your UPS system.

Avoid the ratings game

Thanks to advances in UPS technology, the potential to cut energy costs by tens of thousands of dollars annually has never been greater. But it’s not going to happen because you bought the 99% efficient UPS system versus the one that’s 97% efficient. While efficiency ratings matter, the high numbers advertised are based on full load levels — Ask for documentation on how the system works at lighter loads. Consider if you expect your data center to be at full load levels when calculating your savings. Bottom line: Don’t assume the UPS with the highest efficiency rating will cut total cost of ownership the most. Make it part of your decision making process, but not the determining factor.

Higher voltage = bigger savings

It might sound strange to think that upping your power distribution voltage can actually save energy, but it can and a lot of it. In most data centers, the UPS delivers power to the server at 208V. By raising your voltage to 240V, you can expect energy savings of 2% or more, depending on the power distribution configuration. Bottom line: Higher voltage is a good thing, and most data centers are equipped to handle it. However, not all UPS systems are, so select one that can provide higher voltage.

“While advances in technology during the past 30 years have dramatically improved the efficiency of UPSs, specifying engineers often had to choose a UPS based on mutually exclusive merits, either highest efficiency or highest protection,” said Jim Davis, three-phase business unit manager, Eaton’s Power Quality and Control Operations. “With the Energy Saver System there is no compromise, a single UPS delivers consistent power quality and protection for IT systems with the highest efficiency across all load ranges.”